COOL AND CLEAR WATER SOURCE is a water refilling station that uses a 21 stage State of the Art water filtration , purification and reverse osmosis system. quality and technology standards to ensure safe and purity of water. COOL AND CLEAR is also a member of WATER QUALITY ASSOCIATION and consistently goes through MONTHLY WATER INSPECTION done by an affiliate of Department of Health. SystemManual
21Stages3000GPD –Supreme Series
Purified Drinking Water
Cool and Clear Water Source
Head Office:Unit 102 Number 419 Bulalakaw st Barangay Plainview Mandaluyong City
Makati Branch : 2089 E. Pascua Street Barangay Carmona Makati City
COMPLETE Filtration / Purification/ Sterilization System
This Package is anadvancedwater Filtrationsystemandpurificationequipmentdesignedfor water refilling stationfor commercial use.A TRUEfiltration and purificationsystemandhas an automatic regenerationprocess, therebyproducing “HIGH”quality drinking water. FROM
WATERSOURCE-DEEPWELL OR NAWASA
WaterpassestoTwo (2) units offilter housing20Slim ( 3/4” InletandOutlet,2.5”x20” long ) , withpleatedtype sedimentcartridgeof50”and30 micronrating( 2.5”x20” long , washable)whichactsasthepre treatment sedimentremoval. PRE – TREATMENTSYSTEM
Pre – TreatmentSediment Filter, to filter the water from suspended solids / anysediments
SuitableforMunicipalandWellWaterapplication
AfterRawWater StorageTank, waterflowstothesystemusingaboosterpumprated1 hp( withcut-in / cut-offrateof20psi / 60psi ),Waterlinearepvcpipesof¾” diameterprotectedwithsafetyvalves.Drainlinesspecsis1” diameterpvcpipeinterconnected tothesystemmaindrainline ( pvcpipe of2”diameter )
FILTRATIONSYSTEM
Multi-Media Sediment Filter 1.5 cu. ft., 10” x 54” , Automatic Backwash with Control Valve.CompletewithTankriseranddrainfittings
Consist of sediment water filtration. Traps / Absorbs /eliminate suspended solids orany
sediments .SuitableforMunicipalandWellWaterapplication
Activated Carbon Filter 1.5 cu. CompletewithTankriseranddrainfittings
Consist of carbon water filtration., Micronratedcarbonfilter, removes/eliminate all undesirable colors, bad taste, foul odors andto absorb organic chemicals including chlorine
Suitable forMunicipal andWellWater application
Water Softener w/ Brine Tank 1.5 cu. CompletewithTankriseranddrainfittings
Convertshard mineralstosoftminerals. A water softener contains resin beads which hold chemically charged ions. When hard water passes through the softener, calcium and magnesium ions are attracted to the charged resin beads. It's the resulting removal of calcium and magnesium ions that produces "soft water." A water softener collects hardness minerals within its conditioning tank and from time to time flushes them away to drain. SuitableforMunicipalandWellWaterapplication
PURIFICATIONSYSTEM
ReverseOsmosis System – consist of’:
One (1) 20Slimfilter housing w/ sediment cartridge, 5 micron
Thepre-filterwith 3/4” inlet and outletandthe cartridgeis 2.5”x20” long .Thepre-filteris the lastfilteringdevicebeforeROMembrane.Itcanremove mattersbiggerthan5micron passingthrough thepre-treatmentsystemandholdposttreatmentmaterialssuchasactivated carbonpowder flushedoutbythewater,throughwhichthepre-filterpreventstheROMembranefromcontamination alsoithelps eliminateany microscopic residue that might go to the reverse osmosis membrane. This is the stage of filtration that willfurther protect the RO membranefrompre mature fouling. One (1) 4x40RO membrane3000 GPD capacity. TheRO Membrane is the keypart of theRO Machine / TheHEART of the system,the most efficient and effective method of water purification. It uses a special, semi-permeable membrane which removes impurities as small as 0.0001 micron (i.e. 0.00000004 inches) in size, cleansing water of all biological impurities, suspended particles, dissolved solids (TDS), Salts, Metals and chemicalsand pushing the un purewater out of the system to the reverse side which is the reject drain line ofthe system. Howit works:
When water is passed through the semi-permeable membrane with pressure, all particles larger than 0.0001 micron are captured in layers of membrane and only the water particles, being smaller, pass through the membrane
One (1) unit special motor
Helpstransportwater to theROMembrane usingsystemrequiredpressure. Two (2) units Flow Meter (5gpm) thatreflects systems product and reject waterreadingperminute
Two (2) units Pressure Gauge, feedpress 0-140psi , system press, 0-300psi. The pressure gaugesaremainlyusedtoshow thewater pressure beforewaterentersthepump,after pumpandafter RO Membrane.Theycan be used tojudgeif the pre-filter cartridgehaslostit’seffectorneedschanging.Thefilterneedschanging ifthepressuregapbetweenthetwo gaugesisverybig.Also, theycanbeusedtoseethepressuregapofeacharray. One (1) unitLow PressureSwitchserveasasafetydeviceusedtocontroltheoperationof theROMachine.Theswitchissetata certain value accordingtoa required waterpressure.Itautomaticallystops themachinewhen thefeedwaterpressure islowerthan thesetvalue toavoidthespecial motor runningdry andtheresultantdamageto the pump
One (1) unit Solenoid Valve which monitorssupplyofwater inthesystem. One (1) unit Regulator Valvemainlyused toadjustthepressureinside the
membranehousing andtoadjusttheratioofpermeateto concentrate.With the help oftheregulatorvalve, itcanbetteradjustthepermeateflowandthepressureinsidethemembranehousing. PRODUCTWATERof0.0001 micronrating flowsdirectlytothe ProductWaterStorageTank,
REJECTWATERflowsdirectlytothedrainlinetodrainbin
Priortodispensing,waterispumptothePolishingprocessusingaboosterpump S/Srated 1hpwithcut-in, cut-offrateof20psi / 60psi .Waterlinearepvcpipesof¾” diameterprotectedwithsafetyvalves. Drainlinesspecsis1” diameterpvcpipeinterconnected tothesystemmaindrainline ( pvcpipe of2”diameter )
POLISHINGandSTERILIZATIONPROCESS
1 Unit 20” slim filter housing w/ polishing cartridge
20 Slimcarbon for polishing stage. To make water crystal clear and shiny
1 Unit 20” slim filter housing w/ carbon block cartridge
20 Slimcarbon for anti-microbial stage. Eliminates disease causingmicro organismcalledcyst.
1 Unit6 GPM UV System
UVSystem6 GPM,Water Sterilization Stage
Finalprocesspriortodispensing,Micro-Organismandother disease causing bacteriaare killed99.99%, therebyassuringyouof a qualitywaterwhich is SAFEandPUREdrinkingwater. MAINTENANCEANDTROUBLE SHOOTING
1.The pre-filter cartridge shall be washed regularly( weekly )and/oraccording to the feed water condition. vTurnoffWatersupply( check valvebeforefilterhousing )
vDepresspressurereleasebutton ,torelievepressurein thefilterhousing
vScrew offthe housingusingspannerwrenchandtake out the cartridge. vFlush the inside of the housing to use tap water. vInstall thewash uppre-filtercartridge in the housing. DONOTOVERTIGHTEN
vDepressthepressurereleasebuttontoreleasetrapped airfromfilter
vCheckforLeaks
1. RO membrane
The life of the membrane can be 1-2 years long if the conditions conform to the requirements. But with the formation of scale, bacteria and other contaminants, the product water flow’s flow rate and quality will get lower gradually:
1.
1. If the product flow rate drops by 15% gradually not because of the reasons of temperature and pressure, the membrane needs chemical cleaning.
1.
1. If the product water quality worsens gradually and exceeds the standard (the change of raw water quality excluded), the membrane needs chemical cleaning.
1.
1. The chemical cleaning shall be carried out by the professionals or under the direction of the professionals. Makati Branch Telephone Numbers: 8962595 / 5465524
Mandaluyong Branch Telephone Numbers : 5324409 / 5465524
09209540256